Short answer: exothermic welding (also called thermite or aluminothermic welding, and widely known by the trade name cadweld) joins two copper or steel conductors by reducing copper oxide with aluminium inside a graphite mould and pouring the resulting molten copper into the joint cavity. The result is a molecular bond with the full current-carrying capacity of the conductor, no mechanical clamp to loosen, and no external power required on site. It is the reference method for buried ground-grid joints, down-conductor splices and steel-to-copper transitions — and it is the joint type most often written into lightning protection and substation earthing specifications.
Specify it when: the joint is buried or otherwise inaccessible, the design life exceeds 20 years, or the joint must survive a lightning impulse current without a resistance step. Use a bolted or compression connector instead where the joint must be removable for testing or where hot work is prohibited.
Conclusion first: the reaction is self-sustaining once ignited and produces roughly 2500 °C of molten copper, which flows into the mould cavity, fuses the conductor ends and solidifies into a single piece of copper. There is no filler metal and no flux — the joint is not a soldered connection and behaves metallurgically like a continuous conductor.
| Joint type | Typical use | Notes |
|---|---|---|
| Cable to cable (tee, splice, cross, parallel) | Ground grid conductors, ring earth electrodes | The highest-volume application; mould profiles are standardised by conductor size |
| Cable to ground rod | Vertical earth electrode head, copper-bonded or galvanized rod | Requires a rod-size-specific mould; check rod diameter before ordering |
| Cable to steel structure | Down conductor to steel column, rebar, tower leg | Uses a steel-surface mould half; surface must be ground bright and dry |
| Copper to galvanized steel transition | Mixed-metal earth systems | Requires a dedicated transition cartridge to limit brittle intermetallic formation |
| Cable to busbar / plate | Equipotential bonding bar, transformer neutral | Plate thickness must match the mould cavity |
For material selection upstream of the joint — copper-bonded versus galvanized steel conductors and rods — see our grounding conductor selection guide.
Conclusion first: almost every failed exothermic joint traces back to one of four causes — wet or dirty conductors, a damp mould or cartridge, the wrong cartridge size, or a mould that was not clamped shut. The joint is unforgiving because the pour happens once and cannot be re-run on the same conductors without cutting them back.
Acceptance is normally visual plus a hammer tap for buried work, with resistance measurement across the joint on critical circuits. Any joint showing less than full cross-section fusion should be cut out and remade — it cannot be repaired in place.
Source note: the reaction temperature and mould service-life figures above are typical industry working values for copper-oxide/aluminium exothermic systems. They are not measured values for any single product — confirm them against the cartridge and mould manufacturer's data sheet for the specific system being installed, and against the applicable earthing standard for the project.
| Criterion | Exothermic weld | Bolted connector | Compression (crimp) |
|---|---|---|---|
| Connection nature | Molecular / metallurgical bond | Mechanical pressure | Mechanical pressure |
| Loosening over time | None — no interface to loosen | Yes — needs periodic re-torque | Low, but depends on die and installer |
| Current capacity | Equal to conductor | Limited by contact area | Limited by contact area |
| Corrosion in buried service | No crevice to trap moisture | Crevice corrosion risk | Crevice corrosion risk |
| Survives lightning impulse | Yes, no resistance step | Can degrade at the interface | Generally yes if correctly crimped |
| Removable / testable | No — destructive to open | Yes | No |
| On-site power or tooling | None (just ignition source) | Torque wrench | Hydraulic or manual crimper |
| Hot-work permit | Usually required | Not required | Not required |
| Skill sensitivity | Moderate — single irreversible pour | Low | Moderate — die and crimp count |
Conclusion first: specify the joint geometry, the conductor sizes and standards, the cartridge sizing rule and the acceptance criterion — not just "exothermic welding". Vague specs are where under-sized cartridges and mixed-metal failures enter a project.
Liaocheng Feiyan New Material Technology Co., Ltd. supplies grounding and lightning-protection materials including copper-bonded and zinc-bonded steel, grounding rods and exothermic welding consumables, and supports joint specification and installer training on substation, telecom and photovoltaic projects. For designing the electrode system that these joints sit in, see how to reduce grounding resistance.
The joint is a molecular bond with the full current-carrying capacity of the conductor, so electrically and mechanically it performs as a continuous conductor rather than as a connection point. It has no contact interface that can loosen or corrode.
Yes, but it requires a dedicated copper-to-galvanized-steel transition cartridge and a steel-surface mould half. Using a standard copper cartridge on galvanized steel produces a brittle joint that can crack.
No. Because there is no mechanical interface and no crevice, buried exothermic joints do not require periodic re-torquing or corrosion inspection, which is why they are specified for inaccessible joints.
Moisture or contamination on the conductors, or a damp cartridge or mould. Store cartridges dry, clean and brighten the conductor ends, and preheat the mould in humid conditions.
In most jurisdictions yes, because the reaction produces an open flame and sparks. Where hot work is prohibited on site, a compression connector is the usual substitute, at the cost of a mechanical interface.
Typically 50 to 100 pours depending on the profile, the conductor size and how carefully the mould is cleaned between joints. A worn sealing surface causes leakage fins and should be replaced rather than over-clamped.