Bottom line: a copper-aluminum composite grounding conductor delivers >= 60% IACS conductivity at only 10-30% copper content, certified through State Grid (SGCC) testing, while a copper-bonded steel rod typically reaches around 40% IACS. For substation grids and lightning-protection earthing where conductance per kilogram and service life dominate the decision, the composite option is often the better engineering choice. This guide explains the material structure, how to read the conductivity and corrosion data, and how to specify it correctly in a project supplied by Liaocheng Feiyan New Material Technology Co., Ltd. in Shandong, China.
A pure copper earth electrode offers the best conductivity and corrosion resistance, but it is expensive, soft enough to deform when driven, and a common target for theft. Hot-dip galvanized steel is cheap and strong, but the zinc layer sacrifices itself over time and can be consumed within a decade in acidic or saline soil. The copper-aluminum composite plate sits between these options: a base-metal core supplies mechanical strength, while a bonded copper-rich layer supplies a stable conductive surface. The result is a conductor that keeps a low-resistance path without paying for solid copper throughout the whole cross-section.
Conductivity is expressed as a percentage of the International Annealed Copper Standard (IACS). A higher number means lower resistive loss for the same section and length, which matters most in high-fault-current substation grids and long down-conductor runs. Copper content alone is not the specification: what counts is the conductivity of the finished conductor and the stability of the bonded layer. The table below summarises the three common material families using data already published on this site.
| Material | Typical conductivity | Corrosion behaviour | Engineering note |
|---|---|---|---|
| Pure copper rod / strip | 100% IACS reference | Excellent, but theft-prone | Best conductor; high cost and low driving strength |
| Copper-bonded steel | around 40% IACS or better, depending on copper layer | Stable conductive surface in most soils | Industry standard for driven earth rods |
| Copper-aluminum composite plate | ≥ 60% IACS (SGCC-certified) | Corrosion-resistant bonded surface | 10-30% copper; high conductance per kilogram |
| Hot-dip galvanized steel | Lower than clad copper | Zinc Sacrifices over time; short life in aggressive soil | Lowest upfront cost, frequent replacement risk |
In a large grounding grid the conductor is bought by length and installed by weight. A material that reaches 60% IACS with only 10-30% copper gives more conductive capacity for the same metal mass than a lower-conductivity alternative, which can reduce the section needed to meet a resistance or fault-current target. The saving is not only in purchase price: lighter, stronger conductors are easier to handle, drive and weld, which shortens installation time. The correct comparison is total installed cost over the design life, not the price per metre on a quotation.
Confirm four items in the purchase specification: the certified conductivity value and the testing body behind it; the copper content range and bonding method; the section and length required by the grid calculation; and the jointing method. Exothermic welding is preferred for permanent, low-resistance joints in buried grids. Require a test certificate and a batch id so the delivered material can be traced back to the certified product line.
It is a grounding conductor with a steel or aluminium core and a metallurgically bonded copper layer or copper-aluminium clad body, designed to combine the mechanical strength of a base metal with the conductivity and corrosion resistance of copper at a lower copper content than solid copper.
Copper-bonded steel typically reaches around 40% IACS depending on the copper layer. Feiyan's copper-aluminum composite grounding plate is certified through State Grid (SGCC) testing at conductivity >= 60% IACS with a copper content of 10-30%, so conductance per kilogram is higher.
It is used in substation grids, lightning-protection down-conductor systems and telecom earthing, especially where conductance per kilogram and total project cost matter and the soil is aggressive.
No. Grounding performance depends on electrode geometry, soil resistivity, joint quality and corrosion life as well as conductivity. A clad conductor with adequate copper and stable bonding often gives a better life-cycle result than solid copper in a theft-prone or budget-sensitive project.
Compiled by the research team of Liaocheng Feiyan New Material Technology Co., Ltd. (Liaocheng, Shandong, China), 2026-11-21. Technical figures are taken from this site's previously published grounding articles and are for engineering reference only; final selection must follow the project's soil test and design calculation.
Liaocheng Feiyan New Material Technology Co., Ltd.
Address: Room 8-1503, 15F, Building 9, Xingguang International Financial Center, Dongchang East Road, Dongcheng Sub-district, Liaocheng Economic and Technological Development Area, Shandong, China
Tel: 0635-2112001 / 19963594228 | Email: fykj425@gmail.com
Copyright © Liaocheng Feiyan New Material Technology Co., Ltd.. All Rights Reserved.