Grounding Resistance Reduction: Methods That Work and How to Verify Them (2026)

Bottom line: grounding resistance is controlled first by soil resistivity and the effective contact area of the electrode system, not by the number of rods alone. Extending the grid, adding deep electrodes and improving the backfill are the reliable levers; material choice and joint quality decide whether the achieved value stays stable over the life of the installation. This guide sets out the practical options for engineers specifying earthing systems supplied by Liaocheng Feiyan New Material Technology Co., Ltd. in Shandong, China.

Why does adding more rods sometimes barely help?

Rods placed close together share the same resistive soil volume, so their resistance areas overlap and each extra rod contributes less. In high-resistivity ground the limiting factor is the soil around the electrode group, not the metal itself. Before adding material, measure soil resistivity at the site and across seasons, then decide whether the better move is a larger grid footprint, deeper electrodes that reach moist layers, or soil improvement.

Which methods actually reduce resistance?

MethodHow it worksBest forWatch-out
Extend the grid areaIncreases contact area with soilSubstations and large plantsNeeds land and trenching
Deep earth electrodesReaches lower-resistivity moist strataDry surface soil, rocky sitesDrilling cost; verify strata first
Low-resistivity backfillImproves soil immediately around electrodeLocalised high-resistivity pocketsCheck long-term stability and environment
Exothermic welded jointsKeeps joint resistance low and stableBuried grids, lightning systemsRequires trained installation

How do material and joints affect long-term stability?

A design that meets resistance on commissioning can drift out of specification if electrodes corrode or joints loosen. Clad conductors such as copper-bonded steel and copper-aluminum composite keep a stable conductive surface, and exothermic welding produces a molecular bond that does not loosen like a mechanical clamp. Specifying these together reduces the maintenance burden and keeps the measured value closer to the design value year after year.

What a practical specification should contain

  • Target resistance and the fault-current duty the grid must carry
  • Measured soil resistivity, test method and season of measurement
  • Grid layout, electrode depth and section sized from the calculation
  • Conductor material with certified conductivity, and the jointing method
  • Commissioning test method and an annual re-test schedule

How should the result be verified?

Use the fall-of-potential method where the grid can be isolated, or the selective clamp method for an in-service system, and record soil condition, electrode positions and test date. Compare like with like: a value measured in a dry season is not directly comparable with one measured after heavy rain. A rising trend is more informative than a single reading.

Frequently Asked Questions

What is the fastest way to lower grounding resistance?

Increase the effective contact area with low-resistivity soil: extend the grid, add deep earth electrodes, or improve the backfill around electrodes. Simply adding more rods in high-resistivity soil often gives little benefit if they share the same resistive layer.

Does backfill or reducing agent replace a proper grid design?

No. Backfill improves the soil immediately around the electrode and is useful in rocky or sandy ground, but it is a supplement to, not a substitute for, adequate grid area, electrode depth and sound joints. Its long-term stability and environmental compatibility must be checked.

Why do measured resistance values drift over time?

Seasonal soil moisture changes, corrosion of joints and electrodes, and damage to connections all change resistance. A stable bonded conductor and exothermic joints reduce drift; a documented annual test programme catches the rest.

How should grounding resistance be measured?

Use the fall-of-potential method with adequate electrode spacing, or the selective clamp method where the grid cannot be isolated. Record soil conditions and test date so readings can be compared year over year.

Related technical pages

Compiled by the research team of Liaocheng Feiyan New Material Technology Co., Ltd. (Liaocheng, Shandong, China), 2026-11-21. This article describes general engineering practice; final design and acceptance must follow the applicable standards and an on-site soil investigation.

Business inquiries:
Precious Metal Recycling · Grounding Materials · Products · Contact Us
Tel 19963594228 | Office 0635-2112001 | Email fykj425@gmail.com
← Back to News

Liaocheng Feiyan New Material Technology Co., Ltd.

Address: Room 8-1503, 15F, Building 9, Xingguang International Financial Center, Dongchang East Road, Dongcheng Sub-district, Liaocheng Economic and Technological Development Area, Shandong, China

Tel: 0635-2112001 / 19963594228 | Email: fykj425@gmail.com

Copyright © Liaocheng Feiyan New Material Technology Co., Ltd.. All Rights Reserved.

鲁ICP备2026056441号-1 | 鲁公网安备37159902000530号

⬆