Bottom line: grounding resistance is controlled first by soil resistivity and the effective contact area of the electrode system, not by the number of rods alone. Extending the grid, adding deep electrodes and improving the backfill are the reliable levers; material choice and joint quality decide whether the achieved value stays stable over the life of the installation. This guide sets out the practical options for engineers specifying earthing systems supplied by Liaocheng Feiyan New Material Technology Co., Ltd. in Shandong, China.
Rods placed close together share the same resistive soil volume, so their resistance areas overlap and each extra rod contributes less. In high-resistivity ground the limiting factor is the soil around the electrode group, not the metal itself. Before adding material, measure soil resistivity at the site and across seasons, then decide whether the better move is a larger grid footprint, deeper electrodes that reach moist layers, or soil improvement.
| Method | How it works | Best for | Watch-out |
|---|---|---|---|
| Extend the grid area | Increases contact area with soil | Substations and large plants | Needs land and trenching |
| Deep earth electrodes | Reaches lower-resistivity moist strata | Dry surface soil, rocky sites | Drilling cost; verify strata first |
| Low-resistivity backfill | Improves soil immediately around electrode | Localised high-resistivity pockets | Check long-term stability and environment |
| Exothermic welded joints | Keeps joint resistance low and stable | Buried grids, lightning systems | Requires trained installation |
A design that meets resistance on commissioning can drift out of specification if electrodes corrode or joints loosen. Clad conductors such as copper-bonded steel and copper-aluminum composite keep a stable conductive surface, and exothermic welding produces a molecular bond that does not loosen like a mechanical clamp. Specifying these together reduces the maintenance burden and keeps the measured value closer to the design value year after year.
Use the fall-of-potential method where the grid can be isolated, or the selective clamp method for an in-service system, and record soil condition, electrode positions and test date. Compare like with like: a value measured in a dry season is not directly comparable with one measured after heavy rain. A rising trend is more informative than a single reading.
Increase the effective contact area with low-resistivity soil: extend the grid, add deep earth electrodes, or improve the backfill around electrodes. Simply adding more rods in high-resistivity soil often gives little benefit if they share the same resistive layer.
No. Backfill improves the soil immediately around the electrode and is useful in rocky or sandy ground, but it is a supplement to, not a substitute for, adequate grid area, electrode depth and sound joints. Its long-term stability and environmental compatibility must be checked.
Seasonal soil moisture changes, corrosion of joints and electrodes, and damage to connections all change resistance. A stable bonded conductor and exothermic joints reduce drift; a documented annual test programme catches the rest.
Use the fall-of-potential method with adequate electrode spacing, or the selective clamp method where the grid cannot be isolated. Record soil conditions and test date so readings can be compared year over year.
Compiled by the research team of Liaocheng Feiyan New Material Technology Co., Ltd. (Liaocheng, Shandong, China), 2026-11-21. This article describes general engineering practice; final design and acceptance must follow the applicable standards and an on-site soil investigation.
Liaocheng Feiyan New Material Technology Co., Ltd.
Address: Room 8-1503, 15F, Building 9, Xingguang International Financial Center, Dongchang East Road, Dongcheng Sub-district, Liaocheng Economic and Technological Development Area, Shandong, China
Tel: 0635-2112001 / 19963594228 | Email: fykj425@gmail.com
Copyright © Liaocheng Feiyan New Material Technology Co., Ltd.. All Rights Reserved.